Fire Engineer Automatic Fire Alarm System Common Test Sites!

Nov 06, 2019

Leave a message

Setting place


1. A factory building for shoes, clothing, toys, electronics, etc. with a building area of more than 1500 m2 or a total construction area of more than 3,000 m2.


2. Each warehouse of cotton, wool, silk, hemp, chemical fiber and its products with an area of more than 1000m2, a cigarette warehouse with an area of more than 500m2 or a total construction area of more than 1000m2.


3. Any store with similar construction area of more than 1500m2 or a total construction area of more than 3000m2, such as shops, exhibitions, financial and trade finance, passenger transportation and freight transportation, with underground or semi-underground shops with a total construction area of more than 500m2.


4. A collection of books or cultural relics, a library with more than 500,000 books, and an important archive.


5. Broadcasting and television buildings, postal buildings, telecommunication buildings, urban or regional power, traffic and disaster prevention command and dispatch buildings.


6. Principal, A, etc., other theaters or cinemas with more than 1,500 seats, more than 2,000 seats or auditoriums, and more than 3,000 seats.


7. Children's housing and other places in large and medium-sized kindergartens, elderly care facilities, ward buildings, hotel buildings and other children's activities in any nursing home with a building area of more than 1500 m2 or a total construction area of more than 3000 m2. 200-bed hospital outpatient building, ward building and surgery department.


8. Song and dance entertainment screening entertainment venues.


9. A technical interlayer with a net height of more than 2.6 m and more combustibles, a net height of more than 0.8 m and a smoldering top or ceiling in the form of combustibles.


10. The main room of the electronic information system and its control room, recording medium library, special valuable or fire hazard machines, instruments, equipment and equipment room, valuables warehouse.


11. In the second-class high-rise public buildings, the combustible goods warehouse with a building area of more than 50m2 and the business hall with a building area of more than 500m2.


12. Other types of high-rise public buildings.


13. Set mechanical smoke, smoke control system, rain or pre-action sprinkler system, fixed fire water cannon fire extinguishing system, gas fire extinguishing system and other places or parts that need to interlock with the fire automatic alarm system.


14. For residential buildings with a building height greater than 100 m, an automatic fire alarm system shall be provided. For residential buildings with a building height greater than 54m but not more than 100m, an automatic fire alarm system shall be provided in the public part, and a fire detector shall be installed in the set. For high-rise residential buildings with a building height of no more than 54m, an automatic fire alarm system should be installed in public parts. When setting up fire protection facilities that require linkage control, an automatic fire alarm system should be installed in the public part. The public part of the high-rise residential building shall be provided with a sound alarm device or emergency broadcast with voice function.


15. A flammable gas alarm device shall be installed in the building where flammable gas or flammable vapor may be emitted.


16. Fire detectors and audible alarm devices or fire broadcasts should be provided for elderly homes and their public walkways in elderly care facilities.